10~35kV overhead insulated cable
Product standard
This product is manufactured according to GB / t14049-2008 10kV and 35kV overhead insulated cables with rated voltage and iec60502 extruded insulated power cables and accessories with rated voltage of 1-30kv.
Usage characteristics
2.1 rated voltage
2.2 the allowable long-term working temperature of cable conductor shall not exceed:
High density polyethylene insulated overhead cable: 75 ℃;
XLPE insulated overhead cable: 90 ℃;
2.3 in case of short circuit (the longest duration shall not exceed 5S), the maximum allowable temperature of cable conductor shall not exceed:
High density polyethylene insulated overhead cable: 150 ℃;
XLPE insulated overhead cable: 250 ℃;
2.4 the ambient temperature during cable laying shall not be lower than - 20 ℃.
2.5 allowable bending radius of cable:
Single core cable: no more than 20 times of the outer diameter of the cable.
Multi core cable: it shall not be greater than 15 times of the outer diameter of the cable.
Model and name of cable
Model | Name | Scope of use |
JKYJ | Copper core XLPE insulated overhead cable | This product is applicable to overhead power transmission lines with AC rated voltage U (UM) of 10 (12) kV and 35 (42) kV. |
JKTRYJ | Flexible copper core XLPE insulated overhead cable | |
JKLYJ | Aluminum core XLPE insulated overhead cable | |
JKLGYJ | Steel cored aluminum stranded core XLPE insulated overhead cable | |
JKLHYJ | Aluminum alloy core XLPE insulated overhead cable | |
JKY | Copper core polyethylene insulated overhead cable | |
JKTRY | Flexible copper core polyethylene insulated overhead cable | |
JKLY | Aluminum core polyethylene insulated overhead cable | |
JKLGY | Steel cored aluminum stranded polyethylene insulated overhead cable | |
JKLHY | Aluminum alloy core polyethylene insulated overhead cable | |
JKLYJ/Q | Aluminum core light XLPE insulated overhead cable | |
JKLHYJ/Q | Steel cored aluminum stranded light XLPE insulated overhead cable | |
JKLY/Q | Aluminum core light polyethylene thin insulated overhead cable | |
JKLHY/Q | Aluminum alloy core light polyethylene thin insulated overhead cable | |
JKLGY/Q | Steel cored aluminum stranded light polyethylene thin insulated overhead cable |
Production scope
Model | Number of cores | Nominal section of conductor(mm2) | |
Rated voltage(KV) | |||
10 | 35 | ||
JKYJ、JKTRYJ、JKLYJ、JKLHYJ、JKLGYJ | 1 | 10~300 | 50~300 |
JKY、JKTRY、JKLY、JKLHY、JKLGY、JKLYJ/Q、 JKLHYJ/Q、JKLY/Q、JKLHY/Q、JKLGYJ/Q、JKLGY/Q |
1 | 10~300 | - |
Main technical parameters of cable
Material Science | Voltage level | Conductor temperature | Current carrying capacity correction factor at actual ambient temperature (℃)K | |||||||||
K V | ℃ | -5 | 0 | 5 | 10 | 15 | 20 | 30 | 35 | 40 | 45 | |
PE | 10 | 75 | 1.57 | 1.46 | 1.41 | 1.36 | 1.34 | 1.29 | 1.15 | 1.08 | 1.00 | 0.80 |
XLPE | 10 | 90 | 1.38 | 1.35 | 1.31 | 1.27 | 1.23 | 1.16 | 1.10 | 1.05 | 1.00 | 0.96 |
XLPE | 35 | 90 | 1.38 | 1.35 | 1.31 | 1.27 | 1.23 | 1.16 | 1.10 | 1.05 | 1.00 | 0.96 |
AC voltage test | |||
Rated voltage | 10kV | 10kV | 35kV |
Ordinary structure insulated structure cable | Light thin insulated structure cable | ||
Test voltage | 18kV/1min . No breakdown | 12kV/1min. No breakdown | 63kV/1min .No breakdown |
BOYI WIRE & CABLE
SERVICE: +86-13001249999
TEL: +86-317-2863988
FAX: +86-317-2863688